1.4520.612 – MIC5 ISE Secondary Open Cylinder 3
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 3 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
1.4520.613 – MIC5 ISE Secondary Open Cylinder 4
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 4 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
1.4520.614 – MIC5 ISE Secondary Open Cylinder 5
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 5 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
1.4520.615 – MIC5 ISE Secondary Open Cylinder 6
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 6 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
1.4520.616 – MIC5 ISE Secondary Open Cylinder 7
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 7 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
1.4520.617 – MIC5 ISE Secondary Open Cylinder 8
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 8 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
1.4520.618 – MIC5 ISE Secondary Open Cylinder 9
Yellow alarm. Initiated by MIC5.
Cause
Corrective action
Disruption in secondary circuit of
cylinder 9 in ignition sequence.
1. Check ignition lead, connector and igniter.
2. Check ignition coil.
100 | Troubleshooting | MS150104/03E 2017-09