608 – AL Wiring PWM_CM6
ZKP-Number: 1.1041.926
Wiring problem at PWM_CM6 channel
Yellow alarm - warning
Cause
Corrective action
Cable break or short circuit on
channel PWM_CM6.
1. Check wiring to connected device or check connected device
itself (actuator/sensor) and replace if necessary (→ Page 194).
2. Contact Service.
609 – AL Wiring PWM_CM7
ZKP-Number: 1.1041.927
Wiring problem at PWM_CM7 channel
Yellow alarm - warning
Cause
Corrective action
Cable break or short circuit on
channel PWM_CM7.
1. Check wiring to connected device or check connected device
itself (actuator/sensor) and replace if necessary (→ Page 194).
2. Contact Service.
610 – AL Wiring HP Fuel Control Block 1
ZKP-Number: 1.1301.902
Wiring faulty at HP fuel control block 1
Yellow alarm - warning
Cause
Corrective action
Cable break or short circuit on
PWM channel, HP fuel control
block 1.
1. Check wiring (→ Page 194).
2. Contact Service.
611 – AL Wiring HP Fuel Control Block 2
ZKP-Number: 1.1302.902
Wiring faulty at HP fuel control block 2
Yellow alarm - warning
Cause
Corrective action
Cable break or short circuit on
PWM channel, HP fuel control
block 2.
1. Check wiring (→ Page 194).
2. Contact Service.
96 | Troubleshooting | MS150120/00E 2014-11
TIM-ID: 0000029153 - 008