153249 – HIHI Knock Integrator A9
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop due to knocking
detected in this cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153250 – HIHI Knock Integrator A10
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop due to knocking
detected in this cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153251 – HIHI Knock Integrator B1
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop due to knocking
detected in this cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153252 – HIHI Knock Integrator B2
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop due to knocking
detected in this cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
153253 – HIHI Knock Integrator B3
Red alarm. Initiated by SAM.
Cause
Corrective action
Emergency stop due to knocking
detected in this cylinder.
1. Check emission values.
2. Check ignition timing (→ Page 137).
3. Check combustion chamber.
4. Check gas quality if feasible (methane number).
MS150058/01E 2012-07 | Troubleshooting | 93