152011 – Error Missing Ring Gear Signal
Red alarm. Initiated by IC922.
Cause
Corrective action
Crankshaft signal for ignition
speed 182 teeth missing.
u
Check sensor B13.2, check sensor clearance and cabling,
replace if necessary. Restart of ignition system required to
restart the engine.
152012 – Error Missing Reset Signal
Red alarm. Initiated by IC922.
Cause
Corrective action
Reset signal from crankshaft is
missing.
u
Check sensor B75, check sensor clearance and cabling, replace
if necessary. Restart of ignition system required to restart the
engine.
152013 – Error Missing Camshaft Signal
Red alarm. Initiated by IC922.
Cause
Corrective action
Camshaft signal for ignition is
missing.
u
Check sensor B1.2, check sensor clearance and cabling,
replace if necessary. Restart of ignition system required to
restart the engine.
152014 – Error Number of Teeth
Red alarm. Initiated by IC922.
Cause
Corrective action
Incorrect number of teeth on
timing wheel detected.
1. Check timing wheel.
2. Check settings.
152015 – Unknown Engine Appl. Code
Red alarm. Initiated by IC922.
Cause
Corrective action
Ignition setting is not correct.
u
Check setting.
152016 – OverSpeed Shutdown
Red alarm. Initiated by IC922.
Cause
Corrective action
Genset has exceeded
admissible speed.
u
Restart ignition system.
152018 – E2PROM Checksum Error
Red alarm. Initiated by IC922.
Cause
Corrective action
Hardware not ready for
operation.
u
Restart ignition system.
78 | Troubleshooting | MS150058/01E 2012-07
TIM-ID: 0000017543 - 001