1.4540.036 – FGP High Limit Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
1.4540.037 – Watchdog Reset
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
1.4540.038 – CAN Flow Demand Failed
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet setting is not correct.
u
Check setting.
1.4540.040 – TecJet Shutdown
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet combined alarm. At least
one other TecJet alarm is pending.
u
Rectify cause of alarm.
1.4540.041 – TecJet Internal Fault
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
u
Restart TecJet.
1.4540.042 – Keyswitch State
Red alarm. Initiated by TecJet.
Cause
Corrective action
Keyswitch cabling missing.
u
Check cabling.
1.4520.232 – Error Missing Ring Gear Signal
Red alarm. Initiated by IC922.
Cause
Corrective action
Missing crankshaft signal.
u
Check sensor, sensor distance and cabling, replace as necessary.
1.4520.233 – Error Missing Reset Signal
Red alarm. Initiated by IC922.
Cause
Corrective action
Missing reset signal.
u
Check sensor, sensor distance and cabling, replace as necessary.
76 | Troubleshooting | MS150098/02E 2016-11
TIM-ID: 0000027854 - 001