Specifications
Table 3. Specifications for ModCon75 Touch CPU
General
I/O Support
Zone relay module includes 9 Zone Alarm,
Horn and Fault relay
Ladder Memory
1MB
Bit Operation
0.13
μs
Battery
Model: CR2032 Lithium battery
Battery Lifetime: 4 years typical at 25
°C
Battery Low detection and indication (via
the HMI panel and via System Tag).
Connectors
IO/COM Bus connector
CANbus connector –
Not Supported, No
Customer Connection
Communication
.
RS485
Voltage limits
-7 to +12 VDC maximum, Differential
Baud rate range
1,200 – 115,200 bps
Nodes
Up to 32
Isolation voltage
500VAC for 1 minute
Cable type
Shielded twisted pair in compliance with EIA
RS485
Cable Length
Maximum 1,200 m (3,937 ft.)
Termination
Set using DIP Switches
Environmental
Protection
IP20, NEMA1
Operating temperature
-20°C to 55°
C
(-4°F to 131°F)
Storage temperature
-30°C to 70°
C
(-22°F to 140°F)
Relative Humidity (RH)
5% to 95% (non-condensing)
Operating Altitude
2,000m (6,562 ft.)
Shock
IEC 60068-2-27, 15G, 11ms duration
Vibration
IEC 60068-2-6, 5Hz to 8.4Hz, 3.5mm constant amplitude,
8.4Hz to 150Hz, 1G acceleration