Command 147: Trim 4mA Loop
This command allows initiation of the 4mA trimming procedure.
Request Data Bytes: None
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8 Response Code
1
Unsigned-8 Device Status
Command 148: Trim 20mA Loop
This command allows initiation of the 20mA trimming procedure.
Request Data Bytes: None
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8 Response Code
1
Unsigned-8 Device Status
Command 149: Read Timer (using index)
Used to read the one of the following internal diagnostic timers, using an index as indicated in table below.
The value of the selected timer is returned as a 32-bit unsigned integer.
Index
Parameter
Read/Write
17
Run Timer
Read
30
Alarm Timer
Read
32
Warning Timer
Read
34
Trouble Timer
Read
36
Maximum Gas Timer Read
38
Minimum Gas Timer Read
Request Data Bytes:
Byte
Format
Description
0
Unsigned-8 Index to select appropriate timer as per table above
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8
Response Code
1
Unsigned-8
Device Status
2
Unsigned-8
Index of selected timer
3-6
Unsigned-32 Value of selected timer
60
SMC 5100-XX-IT Toxic Gas Detector Module
13 HART
US
Summary of Contents for 5100-03-IT
Page 5: ...15 5100 88 IT Dimensions 67 SMC 5100 XX IT Toxic Gas Detector Module 5 US...
Page 20: ...mA Circuit Types 20 SMC 5100 XX IT Toxic Gas Detector Module 4 Installation US...
Page 50: ...12 Modbus Memory Map 50 SMC 5100 XX IT Toxic Gas Detector Module 12 Modbus Memory Map US...
Page 51: ...13 HART SMC 5100 XX IT Toxic Gas Detector Module 51 US 13 HART...
Page 52: ...52 SMC 5100 XX IT Toxic Gas Detector Module 13 HART US...
Page 68: ......