Command 131: Set Alarm Level
Used to set the following internal device parameters (variables), with appropriate index. Reading of these parameters is
achieved using Command 132.
Index
Parameter
Read/Write
1
Alarm Level Setpoint
R/W
2
Warning Level Setpoint
R/W
3
Calibration Gas Value
R/W
4
Force Gas Value
R/W
5
Maximum Gas Value
Read
6
Minimum Gas Value
Read
7
Display Gas Value During Calibration Read
8
Range
Read
9
Force Trouble Condition
R/W
Request Data Bytes:
Byte
Format
Description
0-1
Unsigned-16 Index to select parameter as per table above
2-5
Float
Value to be written to parameter
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8
Response Code
1
Unsigned-8
Device Status
2-3
Unsigned-16 Index of selected parameter
4-7
Float
New value of selected parameter
Command 132: Read Device Values (using index)
Used to read the values of parameters in table shown in Command 131, with appropriate index.
Request Data Bytes:
Byte
Format
Description
0-1
Unsigned-16 Index to select parameter as per table above
Response Data Bytes:
Byte
Format
Description
0
Unsigned-8
Response Code
1
Unsigned-8
Device Status
2-3
Unsigned-16 Index of selected parameter
4-7
Float
Value of parameter
SMC 5100-XX-IT Toxic Gas Detector Module
55
US
13 HART
Summary of Contents for 5100-03-IT
Page 5: ...15 5100 88 IT Dimensions 67 SMC 5100 XX IT Toxic Gas Detector Module 5 US...
Page 20: ...mA Circuit Types 20 SMC 5100 XX IT Toxic Gas Detector Module 4 Installation US...
Page 50: ...12 Modbus Memory Map 50 SMC 5100 XX IT Toxic Gas Detector Module 12 Modbus Memory Map US...
Page 51: ...13 HART SMC 5100 XX IT Toxic Gas Detector Module 51 US 13 HART...
Page 52: ...52 SMC 5100 XX IT Toxic Gas Detector Module 13 HART US...
Page 68: ......