![mru SWG100 CEM User Manual Download Page 100](http://html.mh-extra.com/html/mru/swg100-cem/swg100-cem_user-manual_1846047100.webp)
MRU GmbH
SWG 100 User Manual
Page
100
of
155
Default configuration
Use the menu
M
EASUREMENT
->
E
XTRAS
–
>
D
EFAULT
S
ETTINGS
for the default configuration:
DEFAULT CONFIGURATION
Parameter
Analog output 4-20mA Alarm output relay contact
4mA
20mA
open
CH4 [ % ]
0
100
less than
50
O2 [ % ]
0
25
more than
1
H2S [ ppm ]
0
1000
more than
300
CO2 [ % ]
0
100
more than
50
H2 [ ppm ]
0
500
more than
500
0
500
more than
500
CH4 ambient [ % ]
0
5
more than
1
CH4 ambient [ %LEL ]
0
100
more than
20
Temperature sensor [ °C ]
0
50
more than
50
Fan rotation [ rpm ]
0
2000
less than
1200
Pump rotation [ rpm ]
0
5000
less than
1500
Sample flow [ l/hr ]
0
60
less than
30
Temperature cooler [°C ]
0
20
more than
10
Net calorific value [MJ/kg ]
0
40
less than
30
Gross calorific value [ MJ/kg ]
0
40
less than
30
Net calorific value [MJ/m3 ]
0
40
less than
30
Gross calorific value [ MJ/m3 ]
0
40
less than
30
Summary of Contents for SWG100 CEM
Page 1: ...SWG100 User Manual MRU GmbH D 74172 Neckarsulm ...
Page 2: ...MRU GmbH SWG 100 User Manual MRU GmbH D 74172 Neckarsulm 2 155 ...
Page 102: ......
Page 142: ...MRU GmbH SWG 100 User Manual Page 142 of 155 13 10 Option NDIR bench for CO2 analysis 0 100 ...
Page 154: ...MRU GmbH SWG 100 User Manual Page 154 of 155 14 Declaration of conformity ...
Page 155: ...MRU GmbH SWG 100 User Manual Page 155 of 155 V1 00 EN ...