SD34002g_e.doc / Sep-13
Page 34 / 60
F04
Range
Default
F04.043
Start-up Mode2: Start-up delay for the switching outputs *)
0 ... 10
0
The start-up delay is suitable to temporary suppress the control function
of a switching output (in general for monitoring of a minimum value).
The machine then is allowed to start up first, prior to activation of the
alarm. The start-up delay becomes active upon power-up of the unit or
after the unit has detected "standstill".
The following settings are available (always for encoder 2):
0 = Start-up delay OFF
1 = timed delay:
001 second
2 = timed delay:
002 seconds
3 = timed delay:
004 seconds
4 = timed delay:
008 seconds
5 = timed delay:
016 seconds
6 = timed delay:
032 seconds
7 = timed delay:
064 seconds
8 = timed delay:
128 seconds
9 = automatic delay until first exceeding of the minimum value
10 = external suppression by means of a control input
F04.044
Standstill Time2: Time for definition of "standstill" of encoder 2
0.00 ... 99,99
sec.
0.00
After the unit has detected "frequency = 0" (see parameter "Wait
Time2"), the unit will continue waiting until "Standstill Time2" has
elapsed and then finally report "standstill of encoder 2".
*)
When you use the start-up delay function with combined modes [encoder1] * [encoder2], always
the longest of both settings will be responsible for start-up