SD34002g_e.doc / Sep-13
Page 21 / 60
Step
State
Key action
Display
Comment
00
Normal operation
Actual value
01
> 2 sec.
F01
Display of the
Parameter group
02
Level:
Parameter group
5 x
F02 … F06
Select group # F06
03
F06.058
Confirmation of F06.
The first parameter of this
group is F06.058
04
Level:
Parameter numbers
2 x
F06.059…
F06.060
Select parameter 060
05
0
Parameter 060 appears in
display, actual setting is 0
06
Level:
Parameter values
8 x
1 …. 8
Setting has been modified
from 0 to 8
07
F06.060
Save the new setting (8)
08
Level:
Parameter numbers
F06
Return to level parameter
groups
09
Level:
Parameter groups
Actual value
Return to normal operation
10
Normal operation
During the general setup procedure all counter activities remain
disabled. New parameter settings become active after return to
normal operation only.
5.3. Direct Fast Access to Presets
To get to the fast access routine, please press both
and
at the same time
This will access the parameter group F01 right away. To change of the settings follow the same
procedure as already described above. Besides the advantage of direct access, the fundamental
difference to general setup is the following:
During the fast access procedure all counter functions remain fully active.
Access is limited to presets; no other parameters can be changed.