Cabinet Cabling
– continued
DRAFT
SC
TM
4812ET RF and Power Cabinet Hardware Installation Manual
Apr 2001
V04.03
116
Ground MUST be connected first. Electric shock hazard
exists if any other sequence is used.
WARNING
Figure 5-11: International and North American AC Load Center Wiring
G
N
AC to Pilot Beacon
L2
L1
FW00475
L
N
G
NOTE:
L = Line
N = Neutral
G = Ground
International AC Load Center
North American AC Load Center
NOTE:
L 1= Line 1
L 2= Line 2
N = Neutral
G = Ground
Power Cabinet AC Current
Requirements
Table 5-32 lists the number of sector–carrier AC current ratings for the
Power Cabinet.
Table 5-32: Power Cabinet AC Current Requirements
Number of Sector–Carriers
1
Number of Rectifiers
Power Cabinet AC Current
Ratings
2
3
3
60A (90A Non–Continuous)
6
4
71A (101A Non–Continuous)
9
5
86A (116A Non–Continuous)
5