Power Cabinet Earth
Ground
The objective of this procedure is to install the Power Cabinet earth
ground cabling.
Materials needed
Table 5-23 lists the quantity and description of the necessary materials.
Table 5-23: Materials Required for Earth Ground Cabling
Cable
Qty
Description
H
1
Ground cable, #3 BSWG (#2–AWG; 35 mm
2
), insulated copper wire.
Customer supplied cable.
Compression Lug
2909780203
1
Two hole lug to attach to the Power Cabinet end of the cable. (This part is
supplied with the installation hardware).
Procedure
Follow the procedures in Table 5-24 to install the earth ground cable.
Table 5-24: Procedure to Install Earth Ground Cables
Step
Action
1
Route the ground cable (H) into the I/O area of the Power Cabinet through the slot in the right cover
panel. Refer to Figure 5-8 for recommended location.
NOTE
Ground cables should maintain a bend radius of 200 mm (8”) or larger.
NOTE
This step is omitted if the ground wire is already in place and entering the cabinet through the concrete
pad.
2
Strip insulation from the Power Cabinet end of the cable.
3
Attach the two hole ground lug supplied with the installation hardware to the stripped end of the cable.
Use the proper crimp tool (CGDSTBM25S or equivalent).
4
Connect the two hole lug to the back of the Power Cabinet (see Figure 5-1 for location) and secure
with the two M6 nuts supplied with the installation hardware. Torque to 5 N–m (45 in–lbs.).
5