59
Morley-IAS
996-203-000-2, Rev. 02
-
Press the
key and the LCD returns to the Timer edit screen with the Finish ‘day’ field now highlighted.
Edit this in the same way as with the Start day and time fields.
-
After programming the timer press the
key to exit and return to the list of programmable timers. The user
is prompted to save the changes; press the
key to save or the
key to exit without saving changes.
-
If no Detection Mode has been programmed (refer to
Section 5.3.10 Detection Modes
) the user is
warned when trying to program a timer, as in the example shown below:
Note:
In the above example, timer 01 has been programmed to start at 08:00 (8:00 am) and finish
at 18:00 (6:00pm) with Sensitivity as the selected Detection Mode. ‘No Action’ indicates that
the timer will have no effect as no Detection Mode operation has been programmed. This will
show: Delayed, Verification, Sensitivity depending on the mode selected.
Note:
This is just a warning to indicate this condition. It will not stop the settings chosen from being
accepted and changed. The timers programmed, however, will have no effect until a valid
Detection Mode action has also been selected.
-
If the finish time entered is before the start time (or if the start time entered is after the finish time
currently programmed) the display briefly shows a warning message as follows.
www.acornfiresecurity.com