34
Morley-IAS
996-203-000-2, Rev. 02
1
Language
English
English
Change the language displayed on the LCD.
Icelandic
2
Date Format
dd/mm/yyyy
Configure the presentation of the date
mm/dd/yyyy
on the LCD.
3
Device Blinking
ON
ON
Determines if the detector’s LED flashes when the
OFF
device is polled by the panel (protocol dependent).
4
Loop Protocol
-
-
Option not available for some markets.
Refer to
Product Market Variations Manual
for
details if this is available for your market.
5
Automatic
YES
YES
YES configures the automatic re-activation
Resound*
of sounders with ANY new alarms after
silencing of sounder outputs.
NO
If NO is configured then no re-activation
of sounders occurs with ANY new alarm after
silencing of sounder outputs.
6
Auto High Test
-
-
Refer to
Product Market Variations Manual
for details if this is available for your market.
7
Sounder Group/
NO
NO
If NO is configured sounder type output devices
Device Disable*
cannot be disabled using the group/device
disablement options only via the global sounder
disablement command.
YES
If YES is configured sounder type output devices can
be disabled via the group/device disablement options.
NOT EN54 COMPLIANT in this mode.
8
Number of Fault
4
4, 5, 6
Number of consecutive polls required before
Polls
device faults are reported.
This setting applies to: DEVICE LEVEL FAULT,
DOUBLE ADDRESS FAULT, NO REPLY FROM
DEVICE, BAD DEVICE REPLY, DEVICE ADDED,
DEVICE NOT SUPPORTED, DEVICE TYPE
CHANGED. Refer to
Product Market Variations
Manual
for protocol-specific fault conditions.
9
Phone
Blank
20 character text
User Information. Configure text for phone
number of service/ maintenance provider.
10
Site Name
Blank
20 character text
User Information. Configure text for Site
Reference Name to be used when the user
``
contacts the service/ maintenance provider.
11
Next Service Due
01/01/00
Date
User Information. Set next service due date
based on agreed maintenance schedule.
User can view this information along with the
Site Name Reference and phone number of
the service provider.
12
Network Option*
NO
NO
Includes the panel as part of a fire detection
YES
network arrangement.
* If a panel is part of a network the Automatic
Resound, Sounder Group/Device Disable and
Network Toplogy settings MUST all be set the
same. Also required for Detection Mode,
Stages 1/ 2 Timers and 7-Day Timers.
5.3.4 General Options
-
From the Commission menu selecting ‘General Options’ displays the first five items in a list of
configurable options.
-
Use the
and
keys to highlight the desired menu item. Use the
/
to step down/ up one
LCD page at a time. Press
to confirm selection. Another menu screen is displayed to allow
further function selection or editing of configuration settings.
Option
Default
Setting
Description
Title
Options