Morley-IAS
996-203-000-2, Rev. 02
5.3
Programming Manually
-
The DX Connexion Series Fire Alarm Control Panels need to be at user access Level 3 before any
commissioning functions can be carried out. Access Level 3 can be accessed the access Level 2
menu, as described below.
5.3.1 Selecting the Commission Option
-
Firstly, select Level 2 Menu functions (refer to the User Manual for further information). The LCD
then displays the Level 2 User Menu. The level 2 user menu, whether entry is by passcode or
keyswitch (if this is fitted and configured for this purpose), presents the same user options. The
menu header, located in the square brackets at the top-left corner of the LCD, indicates the method
of entry to access this menu; default passcode (U0) or keyswitch (U9). The menu shown below
indicates that the default passcode was used.
-
To select the Commission mode functions, press ‘7’. If this is done at user access Level 2, the
display will then prompt for entry of the access Level 3 passcode.
-
Enter the Level 3 passcode and press
to confirm. The LCD prompts the user to unlock the
memory.
-
Press the ‘0’ key to exit the Commission Menu and return to the access Level 2 user menu. Press
the
key to return to the access Level 1 menu.
-
If entering the access Level 3 passcode at the prompt the ‘service level’ menu (S1) is displayed
instead:
-
Press
again to unlock the memory. The Commission Menu options are displayed as follows:
Note:
If the Level 3 passcode is used to confirm entry to the Level 2 Menu options, the panel is
already in Level 3 access mode and, therefore, will not prompt for entry of the Level 3 passcode
when the Commission option is selected.