37
Morley-IAS
996-203-000-2, Rev. 02
-
Refer to
Section 5.1.3 Text Entry
for details on text editing. When finished with editing text, press
the
key to confirm the text entry/ changes and the LCD returns to the device edit screen.
5.3.5.1.2 Edit Zone Assignment
-
With the zone number option shown, press the
key to increment or the
key to decrement the
zone number. Alternatively, using the numeric keys to enter the new zone number.
-
Press the
key to save the changes. The LCD returns to the device editing screen.
Note:
Zone monitor modules must always be allocated to a unique zone number.
5.3.5.1.3 Edit Group Disable Assignment
-
With the disablement group option selected, press either
/
key to move the highlight to change
the disablement group assignment or press the numeric key to select the appropriate option. A
device can be assigned to: No Group (0); Group 1 (1); Group 2 (2); Both Groups (1+2).
-
Press the
key to save the changes. The LCD returns to the device edit screen.
Note:
Care must be taken to avoid using more than one input switch with Disable Group assignments
to prevent situations occurring where it is unclear what the disablement group’s status is.
-
Refer to the User Manual (PN: 996-202-000-X) for details on how to enable/disable a group.
5.3.5.1.4 Input Actions
-
Additional options are presented for input devices such as monitor and zone monitor modules and
for the input circuit of a combined input/ output module. Use the
and
keys to view the complete
range of options.
-
The following table defines each of the possible input actions and whether it is recommended that it
should be set to latching or non-latching.
-
The setting for the latching parameter is set automatically to the recommended value when the
input action is changed.