PARISON CONTROLLER
moog
Moog Italiana srl - Bergamo
MAN145-UM-D01A-EN
81
4.9
Setup Accumulator.
Figure 79
Setup Accumulator:
Setup accumulator page in accumulator position mode.
Access:
From Accumulator Page key
F1
.
Use:
The input calibration should be made in this way: it is possible to indicate a voltage to be
applied on extrusion control output and activate empty accumulator calibration procedure.
The system automatically detects mechanical end-of-stroke, stores this value and
interrupts extrusion control. Using manual movements, the accumulator should be brought
to empty and full position and it is possible to manually confirm the two positions.
The analogical input referred to 100% (V. Full) has to be greater than the analogical input referred
to 0% (V. Empty).
4.9.1
Digital Accumulator.
Digital
Accumulator
:
to
externally
manage the accumulator without the profile
speed control (if YES).
The parison controller catches only the feedback position to manage the movement of the head.
Operation:
Select the operation mode of the accumulator:
Work:
in work mode the loop is closed, the
machine works normally. No calibration is
active. The calibration points are those
written in the fields V. Full and V. Empty.
Summary of Contents for IMI220-145D001
Page 1: ...MOOG Manual IMI220 145D001 Parison Controller...
Page 25: ...PARISON CONTROLLER moog Moog Italiana srl Bergamo MAN145 UM D01A EN 25 Figure 26...
Page 45: ...PARISON CONTROLLER moog Moog Italiana srl Bergamo MAN145 UM D01A EN 45 Figure 37 UNIT mm...
Page 46: ...PARISON CONTROLLER moog 46 MAN145 UM D01A EN Moog Italiana srl Bergamo Figure 38 UNIT mm...
Page 54: ...PARISON CONTROLLER moog 54 MAN145 UM D01A EN Moog Italiana srl Bergamo...