Moog ACV with CANopen bus interface
8 Diagnostics
Troubleshooting
B99224-DV018-D-211, Rev. A, October 2018
291
8.4.1.42 0x5B: CAN general fault
8.4.1.43 0x5E…0x61: CAN RPDO1…4 time out
8.4.1.44 0x62…0x65: CAN RPDO1…4 data
8.4.1.45 0x66…0x69: CAN TPDO1…4 time out
Error Code:
0x5B
Error Name:
CAN general fault
Description:
A general problem in the CAN fieldbus initialization or communication was detected.
A problem in the Network State Machine occurred.
Chapter "2.8.3 Process data object (PDO) protocol", page 18
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check CAN state machine
• Check CAN communication interface settings
• Restore all communication parameters to factory settings
Chapter "9.2 Restoring parameters to factory settings", page 297
If the error still occurs after restarting the valve, send the valve back to factory for
service.
Error Code:
0x5E…0x61
Error Name:
CAN RPDO1…4 time out
Description:
A timeout on CAN Receive PDO 1…4 occurred.
Chapter "2.8.3 Process data object (PDO) protocol", page 18
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check CAN communication interface settings
• Check CAN TPDO timeout settings
Error Code:
0x62…0x65
Error Name:
CAN RPDO1…4 data
Description:
A problem with the parametrization on CAN Receive PDO 1…4 was detected.
Chapter "2.8.3 Process data object (PDO) protocol", page 18
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check CAN communication interface settings
Error Code:
0x66…0x69
Error Name:
CAN TPDO1…4 time out
Description:
A timeout on CAN Transmit PDO 1…4 occurred.
Chapter "2.8.3 Process data object (PDO) protocol", page 18
Severity of error:
Application specific
Action:
• Check cable and cable connection
• Check CAN communication interface settings
• Check CAN TPDO timeout settings