RP424PFC Indoor Gas Fireplace
Page 50
XG0781 - 151104
Installation
Figure 102.
Test flame (end view)
Figure 101.
Test flame (side view)
After installing all chosen media and glass, light the fireplace to ensure
the desired flame is achieved. A gap in the glass can cause a draft
which will make the flame at the front of the fireplace lean to one side.
Check the pilot height:
Figure 103.
Section 11: First Fire
If driftwood logs have been installed, check the logs for carboning
and reposition if necessary.
Ignition Sequence
Refer to the lighting instructions on
Page 53
for information on how
to light the appliance. These instructions may also be found inside
the control box.
When the fireplace ON/OFF wall switch is placed in the ON position,
the following sequence of events should take place:
The
Heat Sensor or Combustion Air Switch
light and
Wall
Switch
light on the control box will be lit.
The power vent will initialize.
There will be a 60 second prepurge delay.
If the accent lights have been turned on they will light.
The igniter will attempt to light the pilot. The igniter will glow for
30 seconds, pause for 30 seconds. This cycle will occur twice before
the system enters a lockout mode. After 5 minutes the system will
attempt to light again.
The pilot will light.
The igniter will stop glowing.
The burner will light.
Allow the fireplace to operate for at least 5 minutes.
Refer to
Troubleshooting
if you encounter any issue during the
ignition sequence.
Figure 103a.
Igniter
Sensor /
Flame Rod