I-Series Indoor Gas Fireplace
Installation
Clearances:
The 34DFID-L
Insert is designed and built to be installed into masonry or manufactured fireplaces. There is no requirement to have
a non-combustible hearth in front of the unit. Clearances to the underside of the mantel or sidewall are measured from the edge of
the door/screen front. The Mantel is shown as 10” maximum at a distance of 17” minimum from the door edge top. The mantel can
be extended further providing that you increase the height proportionately. For instance, if you want a mantel that is 2” beyond the
10” maximum, you have to install it 2” above the 17” minimum.
Figure 2 Sec.2
34DFID-L clearances
10"
254
Max
17"
432
Min
8 12 "
216
Min.
Mantel
Side Wall
Hearth Protection
Not Required
Faceplate
17"
432
Minimum
10"
254
Max
Allowable
Mantel
Area
25"
27"
29"
31"
33"
35"
37"
39"
10"14"18"24"26"30"34"38"
21"
19"
17"
23"
Section 2: Installation
Figure 1 Sec.2
34DFID-L installation dimensions (Standard Trim)
Install Dimensions:
The install size requirements of your fireplace insert are dependent
on several factors. Gas line location, electrical connection and
gas line type can play into what the minimum installation size
can be. The diagram below illustrates the smallest possible size
requirement of this model. Please take into consideration these
other factors when determining if this appliance will fit into your
masonry or manufactured fireplace.
24"
610mm
34"
864mm
15"
381mm
Gas and Electrical
Supply at Right Side
6"
152mm
24"
610mm