Error Codes
72
02/02 AWB27-1300-GB
42
66
Time access disabled (“lock_time”)
The “lock_time” function block input is activated in the partner station. The station
will perform service 21 whereupon the system clock of the partner station will be
overwritten.
Select another service to be performed at the partner station or deactivate the
“lock_time” function block input of the partner station.
43
67
Flash access disabled (“lock_flash”)
The “lock_ flash” function block input is activated in the partner station. The station
will perform service 13 whereupon the data will be written to the FLASH of the
partner station.
Select another service to be performed or deactivate the “lock_ flash” function
block input of the partner station.
44
68
“fixed_length” parameter incorrect.
The value entered at the “fixed_length“ function block input does not match the
parameter in the partner station. For all stations, set an identical value for
“fixed_length” and perform a block reset.
45
69
Data length of a fixed length frame incorrect
The parameter entered at the “fixed_ length” function block input is equal to 0 or
exceeds the set parameter of the data array.
Check the parameter and enter a permissible value for “fixed_length”.
46
70
Data length or offset address incorrect
The addition of the parameters entered at the “tra_variable_length” and
“tra_source_offset” and “tra_destination_offset” function block inputs exceeds
the value entered in the variables declaration for the constants “tra_dfl_max” or
“rec_dfl_max”.
Check the parameters and enter a permissible value for the variables.
The impermissible value 0 has been entered at the “tra_variable_length” function
block input. Enter a permissible value.
47
71
Subaddress too large
The parameter entered at the “tra_subaddress” function block input exceeds the
value of the constants “tra_sub_max” or “rec_sub_max” set in the variables
declaration.
Check the parameter and enter a permissible value for “tra_subaddress”.
Error code
Meaning
hex
dec