![Moeller S40-AM-TD Manual Download Page 74](http://html1.mh-extra.com/html/moeller/s40-am-td/s40-am-td_manual_1819281074.webp)
Telecontrol function blocks
71
02/02 AWB27-1300-GB
Error codes of the partner station
Table 15 describes the error codes that are generated in a
partner station. These error codes are output at the
“fail_code” output of the function block of the telecontrol
station and partner station.
Table 15:
Partner station error messages
3E
62
Timeout CTS signal
The modem does not respond to the RTS signal of the telecontrol module.
Check the functional reliability of the connected modem and of the connecting lead.
3F
63
Timeout error
The telecontrol partners are not responding.
7F
127
Communication error
The data received by the station is unintelligible.
Ensure that
– all stations have the same baud rates,
– there are no faults on the transmission lines
– the modems are operating correctly.
– the time parameters of the program cycle time are adjusted (
Error code
Meaning
hex
dec
Error code
Meaning
hex
dec
40
64
Invalid communication reference
After a connection has been established successfully, no corresponding
communication reference is discovered at the partner station. Check the entries in
the “com_ref_n” function block inputs.
41
65
Data access disabled (“lock_data”)
The “lock_data” function block input is activated in the partner station and the
station performs a service whereby data is written to the partner station RAM.
Select the station, choose another service for execution or deactivate the
“lock_data” function block input of the partner station.
Summary of Contents for S40-AM-TD
Page 7: ...4 02 02 AWB27 1300 GB ...
Page 11: ...8 02 02 AWB27 1300 GB ...
Page 27: ...24 02 02 AWB27 1300 GB ...
Page 77: ...74 02 02 AWB27 1300 GB ...