Parameter function block
37
02/02 AWB27-1300-GB
Table 5:
Inputs for the telecontrol function
Inputs
Data
type
Value
range
Description
strobe
BOOL
0/1
Start of the service defined at “command”.
Active only when “ready” =1
requested_station
USINT
1 to x
Partner station to which a connection is to be
established.
The upper value limit depends on the telecontrol
function block selected.
command
USINT
10 to 33
Command code for the services offered,
lock_data
BOOL
0/1
“lock_data” = 1 disables the writing of the
data array.
lock_time
BOOL
0/1
“lock_time” = 1 means that time
synchronisation is disabled.
lock_flash
BOOL
0/1
“lock_flash” = 1 means that writing of the flash
is disabled or is not available.
user_status_1
BOOL
0/1
User status bit 1
user_status_2
BOOL
0/1
User status bit 2
user_status_3
BOOL
0/1
User status bit 3
user_status_4
BOOL
0/1
User status bit 4
tra_status
WORD
0 to 65535
Status word
The status word is automatically transferred
after every connection establishment and when
service 31 is carried out between stations
(is indicated in the partner station in the
status array).
tra_variable_
length
USINT
–
Data length in the case of variable length frames.
tra_subaddress
USINT
0 to 255
Definition of the subaddress for variable length
frames
tra_source_offset
USINT
0 to 219
Source offset address for variable length frames