10
Redundant Power supply
The DTS 4160 permits different power supply alternatives:
1. Non-redundant power supply:
Only one power connector is plugged in (24VDC or 240VAC)
Notice:
In the menu: ‘2 Configuration’
‘4 General’
‘3 Power’ must be set to
'0=single'.
2. Redundant power supply:
More than one power connector is plugged in.
To guarantee a full surveillance of the inputs, following variants are possible
:
Supply1:
Supply2:
Variant 1
Mains supply
DC in 1
Variant 2
Mains supply
DC in 2
Variant 3
DC in 1
DC in 2
Supply is checked once per minute for correct functioning. The alarm 03: ‘Failure red.
supply’ is set in case of error.
Notice:
In the menu: ‘2 Configuration’
‘4 General’
‘3 Power’ must be set to
'1=redundant'.
Notice:
All power supply inputs are working and can be used regardless off the
configuration. The configuration advises the DTS to supervise both power
supplies and generate a possible alarm.