© MOBATIME
46 / 124
801214.10
6.5.15 DCF settings
DTS 4160.grandmaster Moser-Baer AG
====================================
DCF SETTINGS
1 Offset correction value 500
2 Max offset to source 500
98 Return and save
99 Return and discard changes
Enter desired menu number>
Path: 2 Configuration
2 Time handling
7 DCF settings
1. Offset correction value: With the offset correction value the cable delay can be
compensated (0ns–10000ns)
2. Max offset to source: Max offset to DCF source to trigger the alarm “Time source
big offset“ (100ns – 5’000’000ns)
Notice:
We recommend that the offset correction value is at least 500ns because
of the hardware delay.
We recommend that a second source is used to calibrate the DCF.
Only a
high precision DCF signal
, e.g. from another DTS 4160/4210 or
from GPS 4500 or GNSS 3000 is supported.
The received DCF signal must contain UTC timezone.
The DCF input only works with DTS device (HW) revision 03 or higher !
6.5.16 E1 settings
DTS 4160.grandmaster Moser-Baer AG
====================================
E1 SETTINGS
1 Max offset to source 500
2 QL option (I-III) 1
98 Return and save
99 Return and discard changes
Enter desired menu number>
Path: 2 Configuration
2 Time handling
8 E1 settings
1. Max offset to source: Max offset to E1 source to trigger the alarm “Time source big
offset“ (100ns – 5’000’000ns)
2. QL option (I – III): This setting is not configurable, because at the moment only
option I of the quality level is supported