background image

 

 

Description: 

The ESI 48/230V inverters are single phase, fan-cooled inverters. They convert all direct voltages from 48 V battery 
systems to an uninterruptible, stabilized AC voltage. The outstanding dynamic performance matches the supply 
requirements for state-of-the-art telecom equipment. This performance as well as the advanced technology is the 
key factors of the success of this inverter and it offers a cost effective and reliable solution. 

 

 
 
 

Features 

• 

Standard 19”, 23”and 25” rack 

• 

1KVA/800W, 2KVA/1600W 

• 

Selectable 208/220V/230V/240V system output 

• 

High efficiency 

• 

Pure sine wave output   

• 

Compact, lightweight modular design 

• 

Bypass function 

• 

RS-232 communication 

• 

User friendly LED and LCD display

 

 

 
 

 

Specification 

General 

Product name

 

ESI 48 / 230 V – 1k VA 

 

ESI 48 / 230 V – 2k VA 

Efficiency, at 230Vrms 

85 %   

Safety UL 

60950 

 EN 

60950 

 CAN/CSA-C22.2 

No. 

60950 

EMI, radiated compliant with 

FCC Part 15 class A   

    

EN 55022 class A 

Cooling Fan 

cooled 

On/Off Switch 

Yes 

MTBF          

450K Hours 

Input 

Input voltage   

40 … 60 V

dc

 

Rated current 

25 A (1k VA) / 50 A (2k VA) 

EMI, conducted 

EN 55022, class A 

Input protection 

Fuse and DC breaker 

AC Input(Bypass) 

Input voltage 

208 / 220 / 230 / 240 V

rms

 ± 20 V

rms

 

Frequency 

50 / 60 Hz ± 5 Hz 

EMI, conducted compliant with  FCC Part 15 class A   
     

EN 55022 class A, EN 55022 class A 

Output 

Output voltage 

208 / 220 / 230 / 240 V

rms

   

Voltage regulation 

< ± 2 % 

Frequency 

50 / 60 Hz ± 0.2 Hz 

THD 

3 %: 100% liner load 

 

5 %: 100% SPS load 

Current, nominal 

5 A

rms

 (1k VA)

 

 10 

A

rms

 (2k VA) 

Crest factor 

3 : 1 

Power, nominal 

1k VA / 800 W 

 

2k VA / 1600 W 

Mechanics 

Width, overall 

17.3” / 440 mm   

Depth, overall 

11.8” / 300 mm 

Height, overall 

3.5” / 88.0 mm 

Weight 

17.6 lb / 8.0 kg (1k VA) 

 

18.7 lb / 8.5 kg (2k VA) 

Environment 

Operating temperature 

0 ... + 45 °C 

Relative humidity 

20 ~ 90 %, non condensing 

Altitude 

- 500 ~ 10000 feet 

*Specifications are subject to change due to technical progress

 

 