© MOBATIME
92 / 124
801214.10
The
ConfigChangedTime
variables show the time of the last change of the relevant
configuration group as TimeTicks value in 1/100th seconds. The management system
can decide on the basis of these time values, which configurations need to be
reloaded. The groups and their parameters are listed in appendix “G Parameters“.
9.3.5
Alive Notification
[dts4160Alive]
Sent out in a configurable interval.
This
Notification
is always sent out, as soon as SNMP and the alarm traps are
activated and a destination address is configured.
The
Notification
sent out contains the following data:
Field
Type
Size
Description
Example
dts4160SysStatus
Unsigned Int
4 Bytes
Contains the internal
system status
66309
dts4160SysAlarms
Byte Array
8 Bytes
64 Bit Alarm flags
1.Byte Bit 0..7
2.Byte Bit 8..15
::
8.Byte Bit 56..63
FFF870FF.FFFFFFFF
¦ ¦ ¦
¦ ¦ 5.Byte
¦ 2.Byte
1.Byte
9.3.6
Alarm Notification
[dts4160Alarm]
Sent out if alarm status changes, i.e.
Notification
is sent out when an alarm flag is set
or deleted.
This
Notification
is always sent out, as soon as SNMP and the alarm traps are
activated and a destination address is configured.
The
Notification
sent out contains the following data:
Field
Type
Size
Description
Example
dts4160TrapAlMsgErrorNr
Byte
1 Byte
No. of the alarm bit (0..63)
3
dts4160TrapAlMsgErrorState Byte
1 Byte
0 = alarm bit was deleted
1 = alarm bit was set
1
dts4160TrapAlMsgErrorTime Unsigned
Int
4 Bytes
PC-time in seconds since
01.01.1970 00:00:00
946684805
dts4160TrapAlMsgErrorText Text
59 Bytes Error text
Failure supply 1