
Chapter Three: Overview
Trip Points
41
Trip Points
The 640 Series controller provides two trip points (Trip Point A and Trip Point B). Each trip
point operates independently and controls an open collector output that can be connected to an
external relay. Each trip point has an adjustment pot, a status LED, and a test jack. Refer to
Figure 13, page 33, for the location of the trip point adjustment pots and LEDs. The test jacks
are located on the side of the unit, as shown in Figure 4, page 18. Refer to How To Adjust the
Trip Point Values, page 46, for instructions on changing the trip point values.
Action of the Trip Points
The trip points can be turned on when the pressure is above or below the trip point value,
depending upon the location of jumpers on the Transducer board. The initial configuration is:
•
Trip Point A is set to trip high; it is on when the pressure is above the trip point (it is off
when the pressure is below the trip point value)
•
Trip Point B is set to trip low; it is on when the pressure is below the trip point (it is off
when the pressure is above the trip point value)
When on, the trip point is connected, through the collector of an NPN transistor, to power
ground. Refer to Trip Point Specifications, page 54, for the ratings. You can use the unit’s trip
point output (available on pins 13 and 14 of the I/O connector) for further process control.
To change the action of a trip point, refer to How To Select the Trip Point Action, page 47.
Summary of Contents for 640A/641A
Page 4: ...116669 P1 Rev C 12 99 MKS Type 640A 641A Pressure Controller...
Page 9: ...Table of Contents vi...
Page 11: ...List of Figures viii...
Page 13: ...List of Tables x...
Page 21: ...Customer Support Chapter One General Information 8 This page intentionally left blank...
Page 45: ...Initial Configuration Chapter Two Installation 32 This page intentionally left blank...
Page 85: ...Model Code Description Appendix D Model Code Explanation 72 This page intentionally left blank...