41
8.8.3 Set-up for the Name and the Maximum Integrated Value of WHM (Step 2)
Set the WHM name, location, and maximum integrated value
1) Enter the WHM name and location.
Enter the connected WHM name and location.
2) Set the maximum integrated value.
Use the “ /
” button or numeric input to set the
WHM maximum integrated value.
3) Clic k [ F i n i s h] button.
At the end of setting, click the [ F i n i s h] button.
* If the [Cancel] button is clicked, the settings are
interrupted and the screen returns to the initial
window.
[Reference]
Shows the communication parameters that must be set at the watt hour meter used.
Name and maximum integrated value settings
Note:
• A name and location up to 16 characters long can be entered.
• Always set the WHM maximum integrated value. If the correct maximum integrated value is not
set, the energy monitoring functions will not operate normally.
• When the WHM maximum integrated value is 0, a warning is displayed. Set the WHM maximum
integrated value.
Model
Baud rate
Parity
Stop bit
Notes
P o w e r R a i l 3 2 3
9 6 0 0 b p s
Fixed
Fixed
AEM31D/485
Fixed
Fixed
Fi xed
CVM-BC-ITF-RS485-C2
9 6 0 0 b p s
N o n e
1 b i t
E D 3 9 d i n -4 8 5
9 6 0 0 b p s
N o n e
1 b i t
BCD used as communications protocol.
Items other than the above do not have to be set because they are fixed for each watt hour meter.