'10 • SCM-SM-094
2)
Air flow direction is controlled according to the indoor temperature and setting temperature.
a)
When 3D auto operation starts
b)
When Indoor temp. – Setting temp. is
<
=
5ºC during cooling and when Setting temp. – Indoor temp. is
<
=
5ºC during
heating, the system switches to the following air flow direction control. After the louver swings left and right sym
-
metrically for 3 cycles, control is switched to the control in c).
c)
After the flap swings for 5 cycles, control is switched to the control in d).
d)
For 5 minutes, the following air flow direction control is carried out.
e)
After 5 minutes have passed, the air flow direction is determined according to the indoor temperature and setting
temperature.
(b)
During DRY Operation (including auto DRY operation)
Flap
Louver
Cooling
Up/down Swing
Heating
Wide (fixed)
Center (fixed)
Flap
Louver
Cooling
Heating
Left/right Swing
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Flap
Louver
Cooling
Up/down Swing
Heating
Center (Fixed)
Wide (Fixed)
Flap
Louver
Cooling
Heating
Horizontal blowing (Fixed)
Slant forwardl blowing (Fixed)
Operation mode
Indoor temp. – Setting temp. 2°C
Setting temp. – Indoor temp. 2°C
At heating
At cooling
Air flow direction contorol
2°C < Setting temp. – Indoor temp. 5°C
2°C < Indoor temp. – Setting temp. 5°C
Indoor temp. – Setting temp. > 5°C
Setting temp. – Indoor temp. > 5°C
The control in d) continues.
Control returns to the control in b).
Control returns to the control in a).
The control in d) continues.
Control returns to the control in b).
Control returns to the control in a).
<
=
<
=
<
=
<
=
Wide (Fixed)
Flap
Air flow selection
Louver
According to DRY operation.
Horizontal blowing (Fixed)
(b) Sleep timer operation
Pr
essing the SLEEP button causes the temperature to be controlled with respect to the set temperature
.
(8) Timer operation
(a) Comfortable timer setting (ON timer)
(c) OFF timer operation
The Off timer can be set at a specific time (in 10-minute units) within a 24-hour period.
If the timer is set at ON when the operation select switch is set at the cooling or heating, or the cooling or heating in auto mode
operation is selected, the comfortable timer starts and determines the starting time of next operation based on the initial value
of 15 minutes and the relationship between the indoor temperature at the setting time (temperature of room temperature sensor)
and the setting temperature.
Summary of Contents for SRR60ZJ-S
Page 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Page 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Page 133: ...132 10 SCM SM 094...
Page 134: ...133 10 SCM SM 094...
Page 135: ...134 10 SCM SM 094...
Page 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Page 153: ...152 10 SCM SM 094...
Page 154: ...153 10 SCM SM 094...
Page 155: ...154 10 SCM SM 094...
Page 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Page 160: ...159 10 SCM SM 094 PJA012D783...