87
-
'10 • SCM-SM-094
Error code
Remote controller:
LED
Green
Red
Indoor
Stays OFF
Keeps flashing
Content
WAIT
Communication error at
initial operation (1/3)
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
When the remote controller
LCD displays “
WAIT
” 2
minutes after the power on.
Diagnosis
Countermeasure
Replace the
power supply fuse.
NO
YES
NO
YES
The remote controller LCD
displays “ ”
2 minutes after the power on.
Turn the breaker off once and then
back on again 3 minutes later.
Is normal condition restored?
YES
NO
NO
YES
NO
Isn’t blown
the power supply fuse (15A or 20A) on the
outdoor unit controller?
Is AC220/240V
detected at the secondary side of
outdoor sub PCB?
Is the
green LED of indoor unit
flashing?
Are wires
connected properly between
the indoor and the outdoor
units?
Is approx.
DC20V detected between
-
on the outdoor unit terminal
block?
YES
NO
Is approx.
DC20V detected between
-
on the indoor unit terminal
block?
NO
YES
WAIT
See next page.
Defective outdoor sub
PCB
¡
Replace.
Defective indoor control
PCB
¡
Replace.
Replace indoor control
PCB.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor sub
PCB
¡
Replace.
Defective connection wire
(broken wire)
Noise
Defective indoor control
PCB
¡
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Blown fuse
• Faulty outdoor sub PCB
• Connection between PCB’s
• Faulty indoor control PCB
• Defective remote controller
• Broken remote controller wire
Note: If any anomaly is detected during communication, the error code E5 is displayed. Inspection procedure is same as above. (Excluding
matters related to connection) When the power supply is reset after the occurrence of E5, the LED will display “
WAIT
”
if the anomaly
continues. If the breaker ON/OFF is repeated in a short period of time (within 1 minute), “
WAIT
”
may be displayed. In such occasion,
turn the breaker off and wait for 3 minutes.
Summary of Contents for SRR60ZJ-S
Page 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Page 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Page 133: ...132 10 SCM SM 094...
Page 134: ...133 10 SCM SM 094...
Page 135: ...134 10 SCM SM 094...
Page 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Page 153: ...152 10 SCM SM 094...
Page 154: ...153 10 SCM SM 094...
Page 155: ...154 10 SCM SM 094...
Page 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Page 160: ...159 10 SCM SM 094 PJA012D783...