(11) Compressor overheat protection
(a) Purpose:
(b) Detail of operation
1)
Discharge pipe temperature (˚C)
(Example) Fuzzy
95
105
115
2)
(12) Current safe
(a) Purpose:
(b) Detail of operation:
Cooling
Heating
Lower limit speed
Item
Model
3 minutes
3 minutes
3 minutes
105 115
95 105
95 105
3 minutes
3 minutes
115
40 ~ 50
60 ~ 80
32 rps
32 rps
32 rps
25 rps
(13) Current cut
(a) Purpose:
(b) Detail of operation:
(14) Outdoor unit failure
(15) Indoor fan motor protection (Refer to the FDTC series by 23 page)
compressor command
(SRF:150)
300
h
(16) Discharge pipe sensor disconnection protection control
(a)
When the compressor command speed is other than 0 rps.
1) Th3(10)-Th3(0) < 8 °C, and Th3(10)-Th2(10) < 5 °C
The compressor command speed is set on A rps for 5 minutes. After 5 minutes, the compressor command speed is set
on B rps for 5 minutes.
2) Th3(20)-Th3(15) < 5 °C :
The compressor command speed is set on 0 rps.
(b)
Once the unit is stopped by this function, it is not restarted.
Notes (1) Th3(X): After compressor operation, the discharge pipe sensor temperature after X minutes.
(2) Th2(X): After compressor operation, the outdoor air sensor temperature after X minutes.
(17) Regulation of outdoor air flow
• Values of A, B
Model
A
B
30 rps
60 rps
SCM40ZJ-S
30 rps
60 rps
SCM45ZJ-S
30 rps
60 rps
SCM50ZJ-S
20 rps
60 rps
SCM60ZJ-S
20 rps
60 rps
SCM80ZJ-S
20 rps
60 rps
SCM71ZJ-S
(a)
The fan operates as follows according to the compressor command speed. (Except during defrost.)
Cooling
Heating
Compressor speed (rps)
Less than 31
More than 66
85 or more
but 85 or less
Outdoor fan speed
6th speed
5th speed
More than 31
but 66 or less
4th speed
3rd speed
Less than 31
More than 46
66 or more
but 66 or less
6th speed
5th speed
More than 31
but 46 or less
4th speed
3rd speed
Cooling
Heating
Compressor speed (rps)
Outdoor fan speed
Model 40: Less than 40
Model 45: Less than 40
Model 50: Less than 48
Model 60: Less than 48
Model 40: 40 or more
Model 45: 40 or more
Model 50: 48 or more
Model 60: 48or more
Model 40: Less than 56
Model 45: Less than 56
Model 50: Less than 61
Model 60: Less than 61
Model 40: 56 or more
Model 45: 56 or more
Model 50: 61 or more
Model 60: 61 or more
6th speed
5th speed
6th speed
5th speed
SCM71, 80 ZJ-S
SCM40~60ZJ-S
(b)
If the outdoor unit’s fan speed drops, the outdoor fan is run for 1 minute at that speed.
2) Control value
Model
Current safe
①
Current safe
②
Current safe
③
Cooling
Heating
Cooling
Heating
Cooling
Heating
SCM 40, 45, 50ZJ - S
10.0
12.0
10.0
10.0
7.5
7.5
SCM 60ZJ - S
11.0
14.0
10.0
10.0
7.5
7.5
SCM 71, 80ZJ - S
13.0
16.0
10.0
10.0
7.5
7.5
Unit: A
Summary of Contents for SRR60ZJ-S
Page 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Page 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Page 133: ...132 10 SCM SM 094...
Page 134: ...133 10 SCM SM 094...
Page 135: ...134 10 SCM SM 094...
Page 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Page 153: ...152 10 SCM SM 094...
Page 154: ...153 10 SCM SM 094...
Page 155: ...154 10 SCM SM 094...
Page 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Page 160: ...159 10 SCM SM 094 PJA012D783...