Remote controller:
LED
Green
Red
Indoor
Content
E60
Compressor rotor lock error
Outdoor
–
7
times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
power supply voltage
OK?
NO
Reset the power supply and restart operation.
YES
Does the compressor start?
Does E59 occur?
NO
YES
Does it
start up normally without
recurrence of
E60.
YES
NO
Does the
compressor run without
occurrence of
E42?
NO
YES
Is the noise
or vibration of compressor
normal?
Is the
output from inverter
checker OK?
YES
YES
NO
NO
NO
Check and correct the
power supply voltage
Correct it based on the
troubleshooting of E59
Correct it based on the
troubleshooting of E42
Defective outdoor main
PCB
ª
Replace.
Replace compressor.
Check compressor for
insulation, resistance.
Replace compressor if
necessary.
Defective outdoor main
PCB
ª
Replace.
2. Error detection method
Compressor rotor position
3. Condition of Error displayed
If it fails again to detect the
rotor position after shifting to
the compressor rotor position
detection operation, the
compressor stops.
4. Presumable cause
• Defective outdoor main PCB
• Anomalous power supply
voltage
• Improper refrigerant amount
and refrigerant circuit
• Defective compressor (motor,
bearing)
Note: Insulation resistance
• The unit is left for long period without power supply or soon after installation, migrated liquid refrigerant may dissolve in the refrigerant oil in the compressor.
In such case insulation resistance decreases upto several M
or lower. If the electric leakage breaker is activated due to low insulation resistance, check followings.
Check whehter the insulation resistance can recover or not, ater 6 hours has passed since power ON.
(By energize the crankcase heater, migrated liquid refrigerant in the refrigerant oil in compressor can be evaporated)
Check whether the electric leakage breake conforms to high-hermonic specifications
(As units has inverter, in order to prevent from improper operation, be sure to use high-hermonic one.)
Summary of Contents for SRR60ZJ-S
Page 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Page 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Page 133: ...132 10 SCM SM 094...
Page 134: ...133 10 SCM SM 094...
Page 135: ...134 10 SCM SM 094...
Page 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Page 153: ...152 10 SCM SM 094...
Page 154: ...153 10 SCM SM 094...
Page 155: ...154 10 SCM SM 094...
Page 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Page 160: ...159 10 SCM SM 094 PJA012D783...