90
-
'10 • SCM-SM-094
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E1
Remote controller
communication circuit error
Keeps flashing
Stays OFF
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it possible to
reset normally by the
power reset?
Does the drain
pump restart automatically
1 minute later?
Turn SW7-1 to OFF.
ON
Remove the wire
connecting
between indoor/outdoor units.
YES
YES
NO
Note (2) Does the remote controller still display “ ” even
after 3 minutes?
Power reset
NO
WAIT
Malfunction by noise
Check peripheral
environment.
Defective indoor control
PCB
ª
Replace.
Defective remote controller
ª
Replace.
2. Error detection method
When normal communication
between the remote controller
and the indoor unit is
interrupted for more than 2
minutes. (Detectable only with
the remote controller)
3. Condition of Error displayed
Same as above
4. Presumable cause
• Defective communication
circuit between remote
controller-indoor unit
• Noise
• Defective remote controller
• Faulty indoor control PCB
Note:
If the indoor unit cannot communicate normally with the remote controller for 180 seconds, the indoor contnrol PCB starts
to reset automatically.
Summary of Contents for SRR60ZJ-S
Page 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Page 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Page 133: ...132 10 SCM SM 094...
Page 134: ...133 10 SCM SM 094...
Page 135: ...134 10 SCM SM 094...
Page 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Page 153: ...152 10 SCM SM 094...
Page 154: ...153 10 SCM SM 094...
Page 155: ...154 10 SCM SM 094...
Page 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Page 160: ...159 10 SCM SM 094 PJA012D783...