'10 • SCM-SM-094
Error code
Remote controller:
LED
Green
Red
Indoor
Content
E8
Heating overload operation
Keeps flashing 1 time flash
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
YES
(2)
Is the air filter clogged?
Is the
indoor heat exchanger
temperature thermistor
connection OK?
Are the
characteristics of indoor
heat exchanger temperature
thermistor OK?
NO
Check the error data with the
remote controller.
YES
Is the unit
operating in the state of
heating overload?
Note (1) Judge if it is in the state of overload or not as follows.
Is there any short-circuit of air?
Isn’t there any fouling or clogging on the indoor heat exchanger?
Is the outdoor fan control normal?
Isn't the indoor and outdoor air temperature too high?
Note (2) For characteristics of indoor heat exchanger temperature thermistor,
see the error display E6.
YES
NO
YES
NO
Error stop
Reset
Indoor heat exchanger temperature (°C)
56
63
Wash.
Defective indoor heat
exchanger temperature
thermistor connector
ª
Correct.
Defective indoor heat
exchanger temperature
thermistor.
Check refrigerant system.
Adjust
2. Error detection method
Indoor heat exchanger
temperature thermistor (ThI-R1,
R2, R3)
3. Condition of Error displayed
When it is detected 5 times
within 60 minutes from initial
detection or when the overload
condition is detected for 6
minutes continuously.
4. Presumable cause
• Clogged air filter
• Defective indoor heat
exchanger temperature
thermistor connector
• Defective indoor heat
exchanger temperature
thermistor
• Anomalous refrigerant system
Note:
During heating operation; After starting compressor, compressor rotation speed is decreased by detecting indoor heat
exchanger temperature (ThI-R) in order to control high pressure.
Summary of Contents for SRR60ZJ-S
Page 52: ...51 10 SCM SM 094 09 SRK DB 087D Service data record form 45...
Page 132: ...131 10 SCM SM 094 page139 and 160 25A 2 Models SCM50ZJ S 60ZJ S...
Page 133: ...132 10 SCM SM 094...
Page 134: ...133 10 SCM SM 094...
Page 135: ...134 10 SCM SM 094...
Page 152: ...151 10 SCM SM 094 127 and 138 3 Ceiling concealed type SRR...
Page 153: ...152 10 SCM SM 094...
Page 154: ...153 10 SCM SM 094...
Page 155: ...154 10 SCM SM 094...
Page 156: ...155 10 SCM SM 094 4 Ceiling cassette 4way compact type FDTC...
Page 160: ...159 10 SCM SM 094 PJA012D783...