2.3. Wireless remote controller mounting
• Place of mounting
• Where it is easy to operate and easily visible.
• Where children can not touch.
• Mounting
Select a position about 1.2 m above the floor, check that signals from the remote
controller are surely received by the indoor unit from that position (‘beep’ or ‘beep-
beep’ receiving tone sounds). After that, attach remote controller holder to a pillar
or wall and set the wireless remote controller.
2. Selecting the installation location
In rooms where inverter type fluorescent lamps are used, the signal from the
wireless remote controller may not be received.
3. Installation diagram
3.1. Indoor unit (Fig. 3-1)
A
Ceiling
B
Grille
C
Obstacle
D
Min. 1000 mm
E
Min. 500 mm (Entire periphery)
If setting the maintenance space for
E
, be sure to leave is a minimum of 700 mm.
4.1. Check the indoor unit accessories (Fig. 4-1)
The indoor unit should be supplied with the following accessories.
Accessory name
Q’ty
1
Installation template
1
2
Washers (with insulation)
4
Washers (without insulation)
4
3
Pipe cover (for refrigerant piping joint)
small diameter (liquid)
1
large diameter (gas)
1
4
Band (large)
6
Band (small)
2
5
Screw with washer (M5
×
25) for mounting grille
4
6
Drain socket
1
7
Insulation
1
8
Fixing screw for
9
3.5
×
1.6 (Black)
2
9
Remote controller holder
1
0
Battely (AAA)
2
A
Wireless remote controller
1
4. Installing the indoor unit
235
20
650
650
(mm)
C
D
E
A
B
Fig. 3-1
■
SUZ-A09/A12
Fig. 4-1
1
2
3
4
6
5
7
8
0
9
A
A
C
A
C
B
Fig. 3-2
3.2. Outdoor unit (Fig. 3-2)
Ventilation and service space
■
SUZ-A09/A12
A
100 mm or more
B
350 mm or more
C
Basically open 100 mm or more without any obstruction in front and on both sides of the unit.
D
200 mm or more (Open two sides of left, right, or rear side.)
■
SUZ-A18
A
100 mm or more
B
350 mm or more
C
500 mm or more
When the piping is to be attached to a wall containing metals (tin plated) or metal
netting, use a chemically treated wooden piece 20 mm or thicker between the wall
and the piping or wrap 7 to 8 turns of insulation vinyl tape around the piping.
Units should be installed by licensed contractor accordingly to local code require-
ment.
■