background image

11

C

D

B

E

Fig. 8-8

8.4. Locking the up/down airflow direction (Fig. 8-9)

The vanes of the unit can be set and locked in up or down orientations depending
upon the environment of use.
• Set according to the preference of the customer.

The operation of the fixed up/down vanes and all automatic controls cannot be
performed using the remote controller. In addition, the actual position of the vanes
may differ from the position indicated on the remote controller.

1

Turn off the main power switch.
Injuries and or an electrical shock may occur while the fan of the unit is rotating.

2

Disconnect the connector for the vane motor of the vent that you want to lock.
(While pressing the button, remove the connector in the direction indicated by the
arrow as shown in the diagram.) After removing the connector, insulate it with
tape.

3

To adjust the desired airflow direction, slowly move the up/down vanes within the
specified range. (Fig.8-10)

Specified range

Up/down airflow

Horizontal 30° Downward 45° Downward 55° Downward 70°

direction

A (mm)

21

25

28

30

• The vanes can be set between 21 and 30 mm.

 Caution:

Do not set the up/down vanes passed the specified range. Condensation could
form on and drop from the ceiling, or the unit could malfunction.

8. Installing the grille

C

B

A

D

B

A

D

Fig. 8-9

A

Button

B

Vane motor

C

Up/down vanes

D

Connector

E

F

A

Fig. 8-10

E

A

D

B

E

C

Fig. 8-11

8.5. Installing the intake grille (Fig. 8-11)

• Perform the procedure that is described in “8.2 Preparing to attach the grille” in

reverse order to install the intake grille and the corner panel.

A

Refrigerant piping of the main unit

B

Drain piping of the main unit

C

Corner panel

* Installation in any position is possible.

D

Position of the levers on the intake grille when sent from the factory.

* Although the clips can be installed in any of four positions.

E

Receiver

8.6. Check

• Make sure that there is no gap between the unit and the grille, or between the grille

and the surface of the ceiling. If there is any gap between the unit and the grille, or
between the grille and the surface of the ceiling, it may cause dew to collect.

• Make sure that the wires have been securely connected.

8.3.4. Wire connection (Fig.8-8)

• Be sure to connect the unit to the connector (white:10-pole/red:9-pole). Next, at-

tach the white glass tube that comes with the main unit so that the tube covers the
connector. Close the opening of the glass tube with the band.

• Make sure that there is no slack in the each lead wire at the fastener on the grille.

A

Fastener (Accessory)

B

White glass tube

C

Connector of the main unit

D

Connector of the grille

E

Band (Accessory)

E

 Measurement standard

position of grille

F

 Up/down vanes

Summary of Contents for SLZ-A18AR

Page 1: ...korrekt bruk innan luftkonditioneringen installeras INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeer...

Page 2: ...esult in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the s...

Page 3: ...1 2 Washers with insulation 4 Washers without insulation 4 3 Pipe cover for refrigerant piping joint small diameter liquid 1 large diameter gas 1 4 Band large 6 Band small 2 5 Screw with washer M5 25...

Page 4: ...hich inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causi...

Page 5: ...C Installation template Accessory D Screw with washer Accessory Fig 4 7 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 s Check that the difference between the heights of the indoor and outdoo...

Page 6: ...rged in the outdoor unit Use leak detector or soapy water to check for gas leaks after connections are com pleted Use refrigerant piping insulation provided to insulate indoor unit connections Insu la...

Page 7: ...valve remains in the same position Confirm that the pressure gage show 0 101MPa 760 mmHg Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas...

Page 8: ...ould cause a fire A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation A Terminal block B Indoor unit Refer to 7 2 C Breaker D 4 core cable...

Page 9: ...he same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra length to connecting cable Both end of connecting cable extension wire are peeled off When too...

Page 10: ...l A Intake grille B Grille C Intake grille levers D Grille hook Fig 8 2 E Hole for the grille s hook F Corner panel G Screw 8 3 Installing the grille Please pay attention because there is a restrictio...

Page 11: ...on 8 Installing the grille C B A D B A D Fig 8 9 A Button B Vane motor C Up down vanes D Connector E F A Fig 8 10 E A D B E C Fig 8 11 8 5 Installing the intake grille Fig 8 11 Perform the procedure t...

Page 12: ...ctronic sound is heard from the indoor unit Press the ON OFF button again to turn the air conditioner off If the indoor unit is operated with the remote controller both the test run and the emergency...

Page 13: ...f the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or no...

Page 14: ...C Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2...

Reviews: