(1) SLZ-A09/A12 (1:1 SYSTEM)

(2) SLZ-A18 (1:1 SYSTEM) OR MULTI

SYSTEM

• Perform wiring as shown in the diagram to the lower left. (Procure the cable locally)

(Fig. 7-3)
Make sure to use cables of the correct polarity only.

A

Connecting cable (4 core) ((2) · · · 2 core)

B

Power supply cable (3 core)
• SLZ-A09/A12 : 1.0 mm

2

 or more

• SLZ-A18

: 1.5 mm

2

 or more

*

Power supply cable and Indoor unit/Outdoor unit connecting cable shall not be lighter than
polychloroprene sheathed flexible cord. (design 245 IEC 57)

C

Indoor terminal block

D

Outdoor terminal block

E

Alway install an earth, longer than other cable.

• Connect the terminal blocks as shown in the diagram below. (Fig. 7-4)

F

Loosen terminal screw

G

Terminal block

H

Lead wire

 Caution:

• Use care not to make mis-wiring.
• Firmly tighten the terminal screws to prevent then from loosening.
• After tightening, pull the wires lightly to confirm that they do not move.

7. Electrical work

Fig. 7-3

Fig. 7-4

7.3. Outdoor unit (Fig. 7-5)

• Connect cable from the indoor unit correctly on the terminal-block.
• Use the same terminal block and polarity as is used with the indoor unit.
• For aftercare maintenance, give extra length to connecting cable.

• Both end of connecting cable (extension wire) are peeled off. When too long,

or connected by cutting off the middle, peel off power supply cable to the size
given in the figure.

• Be careful not to contact connecting cable with piping.

 Caution:

• Use care not to make mis-wiring. (Fig. 7-6)
• Firmly tighten the terminal screws to prevent them from loosening.
• After tightening, pull the wires lightly to confirm that they do not move.

 Warning:

• Be sure to attach the service panel of the outdoor unit securely. If it is not

attached correctly, it could result in a fire or an electric shock due to dust,
water, etc.

• Tighten terminal screws securely.
• Wiring should be done so that the power lines are not subject to tension.

Otherwise, heat may be generated or fire may occur.

A

Loosen terminal screw

B

Terminal block

C

Lead wire

A

B

C

Fig. 7-5

Fig. 7-6

B

C

A

8. Installing the grille

8.1. Check the grille accessories (Fig. 8-1)

• The grille should be supplied with the following accessories.

Accessory name

Q’ty

Remark

1

Grille

1

650 

×

 650 (mm)

2

Screw with washer

4

M5 

×

 0.8 

×

 25 (mm)

3

Gauge

1

4

Fastener

2

5

Band

2

Fig. 8-1

1

4

5

2

3

A

Cord clamp.

B

Service panel

C

Fixing screws

Summary of Contents for SLZ-A18AR

Page 1: ...korrekt bruk innan luftkonditioneringen installeras INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeer...

Page 2: ...esult in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the s...

Page 3: ...1 2 Washers with insulation 4 Washers without insulation 4 3 Pipe cover for refrigerant piping joint small diameter liquid 1 large diameter gas 1 4 Band large 6 Band small 2 5 Screw with washer M5 25...

Page 4: ...hich inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causi...

Page 5: ...C Installation template Accessory D Screw with washer Accessory Fig 4 7 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 s Check that the difference between the heights of the indoor and outdoo...

Page 6: ...rged in the outdoor unit Use leak detector or soapy water to check for gas leaks after connections are com pleted Use refrigerant piping insulation provided to insulate indoor unit connections Insu la...

Page 7: ...valve remains in the same position Confirm that the pressure gage show 0 101MPa 760 mmHg Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas...

Page 8: ...ould cause a fire A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation A Terminal block B Indoor unit Refer to 7 2 C Breaker D 4 core cable...

Page 9: ...he same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra length to connecting cable Both end of connecting cable extension wire are peeled off When too...

Page 10: ...l A Intake grille B Grille C Intake grille levers D Grille hook Fig 8 2 E Hole for the grille s hook F Corner panel G Screw 8 3 Installing the grille Please pay attention because there is a restrictio...

Page 11: ...on 8 Installing the grille C B A D B A D Fig 8 9 A Button B Vane motor C Up down vanes D Connector E F A Fig 8 10 E A D B E C Fig 8 11 8 5 Installing the intake grille Fig 8 11 Perform the procedure t...

Page 12: ...ctronic sound is heard from the indoor unit Press the ON OFF button again to turn the air conditioner off If the indoor unit is operated with the remote controller both the test run and the emergency...

Page 13: ...f the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or no...

Page 14: ...C Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2...

Reviews: