background image

6

a

d

c

b

e

f

90

°

d

c

b

a

5. Refrigerant piping work

b

a

a

b

e

b

c

d

c

A

c

b

a

d

e

f

g

h

i

5.2. Flaring work

• Main cause of gas leakage is defect in flaring work.

Carry out correct flaring work in the following procedure.

5.2.1. Pipe cutting (Fig. 5-3)

• Using a pipe cutter cut the copper tube correctly.

5.2.2. Burrs removal (Fig. 5-4)

• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in

order to avoid burrs drop in the tubing.

5.2.3. Putting nut on (Fig. 5-5)

• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube

having completed burr removal.
(not possible to put them on after flaring work)

5.2.4. Flaring work (Fig. 5-6)

• Carry out flaring work using flaring tool as shown at the right.

Dimension

Pipe diameter

A (mm)

(mm)

When the tool for R410A is used

B       (mm)

Clutch type

6.35

0 - 0.5

9.1

9.52

0 - 0.5

13.2

12.7

0 - 0.5

16.6

Firmly hold copper tube in a die in the dimension shown in the table at above.

5.2.5. Check (Fig. 5-7)

• Compare the flared work with a figure in rightside hand.
• If flare is noted to be defective, cut off the flared section and do flaring work again.

5.3. Refrigerant and drainage piping locations (Fig.5-8)

A

Drain pipe

B

Ceiling

C

Grille

D

Refrigerant pipe (liquid)

E

Refrigerant pipe (gas)

F

Water supply inlet

G

Main unit

5.4. Pipe connection (Fig. 5-9)

Indoor unit

1) When using commercially available copper pipes:

• Apply thin layer of refrigerant oil to pipe and joint seating surface before tightening

flare nut.

• Use two wrenches to tighten piping connections.
• Air-purge the refrigerant piping using your own refrigerant gas (don’t air-purge the

refrigerant charged in the outdoor unit).

• Use leak detector or soapy water to check for gas leaks after connections are com-

pleted.

• Use refrigerant piping insulation provided to insulate indoor unit connections. Insu-

late carefully following shown below.

2) Heat insulation for refrigerant pipes:

1

Wrap the enclosed large-sized pipe cover around the gas pipe, making sure that
the end of the pipe cover touches the side of the unit.

2

Wrap the enclosed small-sized pipe cover around the liquid pipe, making sure
that the end of the pipe cover touches the side of the unit.

3

Secure both ends of each pipe cover with the enclosed bands. (Attach the bands
20 mm from the ends of the pipe cover.)

See that stop valve on outdoor unit is fully shut (unit is shipped with valve shut). After
all piping connections between indoor and outdoor unit have been completed,
vaccuum-purge air from system through the service port for the stop valve on the
outdoor unit.
After completing procedures above, open outdoor unit stop valves stem fully. This
completes connection of refrigerant circuit between indoor and outdoor units. Stop
valve instructions are marked on outdoor unit.

a

Copper tubes

b

Good

c

No good

d

Tilted

e

Uneven

f

Burred

Fig. 5-3

Fig. 5-4

a

Burr

b

Copper tube/pipe

c

Spare reamer

d

Pipe cutter

Fig. 5-5

Fig. 5-6

Fig. 5-7

Fig. 5-8

J

H

I

B

,

C

F

G

Fig. 5-9

A

Refrigerant pipe and insulating material
(Procure locally)

B

Pipe cover (large) (Accessory)

C

Pipe cover (small) (Accessory)

D

Refrigerant pipe (gas)

E

Refrigerant pipe (liquid)

F

Band (Accessory)

G

Cross-sectional view of connection

H

Refrigerant pipe

I

Insulating material

J

Squeeze

a

Flare nut

b

Copper tube

a

Flaring tool

b

Die

c

Copper tube

d

Flare nut

e

Yoke

a

Smooth all around

b

Inside is shining without any scratches

c

Even length all around

d

Too much

e

Tilted

f

Scratch on flared plane

g

Cracked

h

Uneven

i

Bad examples

A

As viewed from A

+0

-0.4

B

Summary of Contents for SLZ-A18AR

Page 1: ...korrekt bruk innan luftkonditioneringen installeras INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeer...

Page 2: ...esult in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the s...

Page 3: ...1 2 Washers with insulation 4 Washers without insulation 4 3 Pipe cover for refrigerant piping joint small diameter liquid 1 large diameter gas 1 4 Band large 6 Band small 2 5 Screw with washer M5 25...

Page 4: ...hich inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causi...

Page 5: ...C Installation template Accessory D Screw with washer Accessory Fig 4 7 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 s Check that the difference between the heights of the indoor and outdoo...

Page 6: ...rged in the outdoor unit Use leak detector or soapy water to check for gas leaks after connections are com pleted Use refrigerant piping insulation provided to insulate indoor unit connections Insu la...

Page 7: ...valve remains in the same position Confirm that the pressure gage show 0 101MPa 760 mmHg Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas...

Page 8: ...ould cause a fire A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation A Terminal block B Indoor unit Refer to 7 2 C Breaker D 4 core cable...

Page 9: ...he same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra length to connecting cable Both end of connecting cable extension wire are peeled off When too...

Page 10: ...l A Intake grille B Grille C Intake grille levers D Grille hook Fig 8 2 E Hole for the grille s hook F Corner panel G Screw 8 3 Installing the grille Please pay attention because there is a restrictio...

Page 11: ...on 8 Installing the grille C B A D B A D Fig 8 9 A Button B Vane motor C Up down vanes D Connector E F A Fig 8 10 E A D B E C Fig 8 11 8 5 Installing the intake grille Fig 8 11 Perform the procedure t...

Page 12: ...ctronic sound is heard from the indoor unit Press the ON OFF button again to turn the air conditioner off If the indoor unit is operated with the remote controller both the test run and the emergency...

Page 13: ...f the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or no...

Page 14: ...C Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2...

Reviews: