4

4.2. Ceiling openings and suspension bolt installation

locations (Fig. 4-2)

• Using the installation template (top of the package) and the gauge (supplied as an

accessory with the grille), make an opening in the ceiling so that the main unit can
be installed as shown in the diagram. (The method for using the template and the
gauge are shown.)

* Before using, check the dimensions of template and gauge, because they change

due to fluctuations of temperature and humidity.

* The dimensions of ceiling opening can be regulated within the range shown in

following diagram; so center the main unit against the opening of ceiling, ensur-
ing that the respective opposite sides on all sides of the clearance between
them becomes identical.

• Use M10 (3/8") suspension bolts.

* Suspension bolts are to be procured at the field.

• Install securely, ensuring that there is no clearance between the ceiling panel &

grille, and between the main unit & grille.

4. Installing the indoor unit

A

Outer side of main unit

B

Bolt pitch

C

Ceiling opening

D

Outer side of Grille

E

Grille

F

Ceiling

G

Min. 500 mm (Entire periphery)

If setting the maintenance space for 

G

, be

sure to leave is a minimum of 700 mm.

H

Maintenance space

I

Fresh air intake

J

Angle

K

Electric component box

*

Note that the space between ceiling panel of the unit and ceiling slab and etc must be 10 to
15 mm to be left.

*

Leave the maintenance space at the electric component box end.

4.3. Installation of duct (in case of fresh air intake)

(Fig. 4-3)

 Caution:

Linkage of duct fan and air conditioner
ln case that a duct fan is used, be sure to make it linked with the air conditioner
when outside air is taken.
Do not run the duct fan only. It can cause dew drop.

Making a duct flange (prepared locally)

• The shape of duct flange shown left is recommended.

Installation of duct flange

• Cut out the cutout hole. Do not knock it out.
• Install a duct flange to the cutout hole of the indoor unit with three 4 

×

 10 tapping

screws which should be prepared locally.

Installation of duct (should be prepared locally)

• Prepare a duct of which inner diameter fits into the outer diamete of the duct flange.
• In case that the environment above the ceiling is high temperature and high humid-

ity, wrap the duct in a heat insulate to avoid causing dew drop on the wall.

A

Duct flange recommended shape

(Thickness:0.8 or more)

B

3-ø5 hole

C

Detail drawing of fresh air intake

D

Indoor unit

E

Ceiling surface

F

3-ø2.8 Burring hole

G

ø73.4 cutout hole

H

Duct flange (Prepared locally)

I

×

 10 Tapping screw (Prepared locally)

J

Duct

4.4. Suspension structure (Give site of suspension

strong structure) (Fig. 4-4)

• The ceiling work differs according to the construction of the building. Buidling con-

structors and interior decorators should be consulted for details.

(1) Extent of ceiling removal: The ceiling must be kept completely horizontal and the

ceiling foundation (framework: wooden slats and slat holders) must be reinforced
in order to protect the ceiling from vibration.

(2) Cut and remove the ceiling foundation.
(3) Reinforce the ends of the ceiling foundation where it has been cut and add ceiling

foundation for securing the ends of the ceiling board.

(4) When installing the unit on a slanting ceiling, interlock a pillow between the ceiling

and the grille and set so that the unit is installed horizontally.

1

Wooden structures

• Use tie beams (single storied houses) or second floor beams (two story houses) as

reinforcing members.

• Wooden beams for suspending air conditioners must be sturdy and their sides

must be at least 6 cm long if the beams are separated by not more than 90 cm and
their sides must be at  least 9 cm long if the beams are separated by as much as
180 cm. The size of the suspension bolts should be ø10 (3/8"). (The bolts do not
come with the unit.)

2

Ferro-concrete structures

Secure the suspension bolts using the method shown, or use steel or wooden hang-
ers, etc. to install the suspension bolts.

A

Unit

B

Grille

C

Pillow

D

Ceiling

E

Rafter

F

Beam

G

Roof beam

H

Use inserts rated at 100-150 kg
each (procure locally)

I

Suspension bolts M10 (3/8") (procure
locally)

J

Steel reinforcing rod

A

B

C

J

H

I

D

E

F G

*B

*B

1

2

Fig. 4-4

Fig. 4-2

B

30

120

120

20

75

100

70

15

G

E

D

F

120

120

92

25

     

+5

27

 

  

0

208

100

Fig. 4-3

D

H

I

J

A

(mm)

C

(mm)

*B: Suspension bolt pitch (see Fig. 4-2 

B

 for details)

Summary of Contents for SLZ-A18AR

Page 1: ...korrekt bruk innan luftkonditioneringen installeras INSTALLATIEHANDLEIDING Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeer...

Page 2: ...esult in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the s...

Page 3: ...1 2 Washers with insulation 4 Washers without insulation 4 3 Pipe cover for refrigerant piping joint small diameter liquid 1 large diameter gas 1 4 Band large 6 Band small 2 5 Screw with washer M5 25...

Page 4: ...hich inner diameter fits into the outer diamete of the duct flange In case that the environment above the ceiling is high temperature and high humid ity wrap the duct in a heat insulate to avoid causi...

Page 5: ...C Installation template Accessory D Screw with washer Accessory Fig 4 7 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 s Check that the difference between the heights of the indoor and outdoo...

Page 6: ...rged in the outdoor unit Use leak detector or soapy water to check for gas leaks after connections are com pleted Use refrigerant piping insulation provided to insulate indoor unit connections Insu la...

Page 7: ...valve remains in the same position Confirm that the pressure gage show 0 101MPa 760 mmHg Pipe length 7 m maximum No gas charge is needed Pipe length exceeding 7 m Charge the prescribed amount of gas...

Page 8: ...ould cause a fire A switch with at least 3 mm contact separation in each pole shall be provided by the air conditioner installation A Terminal block B Indoor unit Refer to 7 2 C Breaker D 4 core cable...

Page 9: ...he same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra length to connecting cable Both end of connecting cable extension wire are peeled off When too...

Page 10: ...l A Intake grille B Grille C Intake grille levers D Grille hook Fig 8 2 E Hole for the grille s hook F Corner panel G Screw 8 3 Installing the grille Please pay attention because there is a restrictio...

Page 11: ...on 8 Installing the grille C B A D B A D Fig 8 9 A Button B Vane motor C Up down vanes D Connector E F A Fig 8 10 E A D B E C Fig 8 11 8 5 Installing the intake grille Fig 8 11 Perform the procedure t...

Page 12: ...ctronic sound is heard from the indoor unit Press the ON OFF button again to turn the air conditioner off If the indoor unit is operated with the remote controller both the test run and the emergency...

Page 13: ...f the refrigerant is charged from the gas phase composition change may occur in the refrigerant inside the cylinder and the outdoor unit In this case ability of the refrigerating cycle decreases or no...

Page 14: ...C Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2...

Reviews: