4 - 25
4 INSTALLATION AND WIRING
4.3 Wiring
4.3.1 Instructions for wiring
DANGER
Completely turn off the externally supplied power used in the system before installation or placing
wiring. Not doing so could result in electric shock or damage to the product.
When turning on the power supply or operating the module after wiring, be sure that the module's
terminal covers are correctly attached. Not attaching the terminal cover could result in electric shock.
CAUTION
Be sure to ground of the earth terminal FG and LG. Not doing so could result in electric shock or
operation failure. (Ground resistance: 100 or less)
When wiring in the Motion controller, be sure that it is done correctly by checking the product's rated
voltage and the terminal layout. Connecting a power supply that is different from the rating or
incorrectly wiring the product could result in fire or damage.
External connections shall be crimped or pressure welded with the specified tools, or correctly
soldered. Imperfect connections could result in short circuit, fire, or operation failure.
Tighten the terminal screws within the specified torque range. If the terminal screws are loose, it could
result in short circuit, fire, or operation failure. Tightening the terminal screws too far may cause
damages to the screws and/or the module, resulting in drop, short circuit, or operation failure.
Be sure there are no foreign matters such as sawdust or wiring debris inside the module. Such debris
could cause fire, damage, or operation failure.
The module has an ingress prevention label on its top to prevent foreign matter, such as wiring debris,
from entering the module during wiring.
Do not remove this label during wiring.
Before starting system operation, be sure to remove this label because of heat dissipation.
This section described instructions for the wiring of the power supply.
(1) Power supply wiring
(a) 24VDC power supply wires should be twisted as dense as possible. Connect
them with the shortest distance.
Also, to reduce the voltage drop to the minimum, use the thickest wires (Up
to 2.0mm
2
) possible.
Use the wires of the following core size for wiring.
Application
Recommended core size
AWG
(Note-1)
24VDC power supply wires
0.34 to 0.37mm
2
#22
I/O equipment
0.3 to 0.75mm
2
(Outside diameter 2.8mm (0.11inch) or less)
#18 to #22
Ground wire
2.0mm
2
or more
#14 or less
(Note-1): AWG stands for "American Wire Gauge". AWG is a unit of the thickness of conducting wire.
Summary of Contents for Q170MCPU
Page 1: ......
Page 19: ...A 18 MEMO ...
Page 81: ...2 54 2 SYSTEM CONFIGURATION MEMO ...
Page 135: ...5 10 5 START UP PROCEDURES MEMO ...
Page 171: ...7 6 7 POSITIONING DEDICATED SIGNALS MEMO ...
Page 225: ...APP 54 APPENDICES MEMO ...
Page 228: ......