65
Param
e
te
r List
Parameter list
4
⎯
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
⎯
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
PI
D
con
tr
ol
127
PID control automatic switchover
frequency
0 to 400Hz, 9999
0.01Hz
9999
128
PID action selection
10, 11, 20, 21, 40, 41,
50, 51, 60, 61, 70, 71,
80, 81, 90, 91, 100, 101,
110, 111, 120, 121, 140,
141
1
10
129
PID proportional band
0.1 to 1000%, 9999
0.1%
100%
130
PID integral time
0.1 to 3600s, 9999
0.1s
1s
131
PID upper limit
0 to 100%, 9999
0.1%
9999
132
PID lower limit
0 to 100%, 9999
0.1%
9999
133
PID action set point
0 to 100%, 9999
0.01%
9999
134
PID differential time
0.01 to 10.00s, 9999
0.01s
9999
By
pa
ss
135
Electronic bypass sequence selection
0, 1
1
0
136
MC switchover interlock time
0 to 100s
0.1s
1s
137
Start waiting time
0 to 100s
0.1s
0.5s
138
Bypass selection at a fault
0, 1
1
0
139
Automatic switchover frequency from
inverter to bypass operation
0 to 60Hz, 9999
0.01Hz
9999
B
ack
lash
m
e
as
ur
es
140
Backlash acceleration stopping
frequency
0 to 400Hz
0.01Hz
1Hz
141
Backlash acceleration stopping time
0 to 360s
0.1s
0.5s
142
Backlash deceleration stopping
frequency
0 to 400Hz
0.01Hz
1Hz
143
Backlash deceleration stopping time
0 to 360s
0.1s
0.5s
⎯
144
Speed setting switchover
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
1
4
PU
145
PU display language selection
0 to 7
1
1
⎯
147
Acceleration/deceleration time
switching frequency
0 to 400Hz, 9999
0.01Hz
9999
148
Stall prevention level at 0V input
0 to 120%
0.1%
110%
C
u
rr
e
n
t d
e
te
ct
io
n
149
Stall prevention level at 10V input
0 to 120%
0.1%
120%
150
Output current detection level
0 to 120%
0.1%
110%
151
Output current detection signal delay
time
0 to 10s
0.1s
0s
152
Zero current detection level
0 to 150%
0.1%
5%
153
Zero current detection time
0 to 10s
0.01s
0.5s
⎯
154
Voltage reduction selection during
stall prevention operation
0, 1
1
1
⎯
155
RT signal function validity condition
selection
0, 10
1
0
⎯
156
Stall prevention operation selection
0 to 31, 100, 101
1
0
⎯
157
OL signal output timer
0 to 25s, 9999
0.1s
0s
Function Parameters
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Summary of Contents for -NAFR-F720-00167-NA
Page 22: ...12 MEMO ...