101
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
4
4.7 Setting of acceleration/deceleration time and
acceleration/deceleration pattern
4.7.1
Setting of the acceleration and deceleration time
(Pr. 7, Pr. 8, Pr. 20, Pr. 21, Pr. 44, Pr. 45, Pr. 147)
Purpose
Parameter that must be set
Refer to page
Motor acceleration/deceleration time
setting
Acceleration/deceleration times
Pr.7, Pr.8, Pr.20, Pr.21,
Pr.44, Pr.45, Pr.147
Starting frequency
Starting frequency and start-time
hold
Pr.13, Pr.571
Set acceleration/deceleration pattern
suitable for application
Acceleration/deceleration pattern
and backlash measures
Pr.29, Pr.140 to Pr.143
Used to set motor acceleration/deceleration time.
Set a larger value for a slower speed increase/decrease or a smaller value for a faster speed increase/decrease.
For the acceleration time at automatic restart after instantaneous power failure, refer to
Pr. 611 Acceleration time at
a restart
(page 154)
.
Parameter
Number
Name
Initial Value
200V class
(400V class)
Setting Range
Description
7
Acceleration time
00340
(00170) or lower
5s
0 to 3600/ 360s
*2
Set the motor acceleration time.
00490
(00250) or higher
15s
8
Deceleration time
00340
(00170) or lower
10s
0 to 3600/ 360s
*2
Set the motor deceleration time.
00490
(00250) or higher
30s
20
*1
Acceleration/
deceleration
reference frequency
60Hz
1 to 400Hz
Set the frequency that will be the basis of
acceleration/deceleration time.
As acceleration/deceleration time, set the
frequency change time from stop to
Pr. 20
.
21
*1
Acceleration/
deceleration time
increments
0
0
Increments: 0.1s
Range: 0 to 3600s
Increments and
setting range of
acceleration/
deceleration time
setting can be
changed.
1
Increments: 0.01s
Range: 0 to 360s
44
*1
Second
acceleration/
deceleration time
5s
0 to 3600/360s
*2
Set the acceleration/deceleration time
when the RT signal is ON.
45
*1
Second
deceleration time
9999
0 to 3600/360s
*2
Set the deceleration time when the RT
signal is ON.
9999
Acceleration time = deceleration time
147
*1
Acceleration/
deceleration time
switching
frequency
9999
0 to 400Hz
The frequency where the acceleration/
deceleration time switches to the time set
in
Pr.44
and
Pr.45
.
9999
No function
*1
The parameters can be set when
Pr. 160 User group read selection
= "0"
(Refer to page 192)
*2
Depends on the
Pr. 21 Acceleration/deceleration time increments
setting. The initial value for the setting range is "0 to 3600s" and the setting
increments is "0.1s".
...
Specifications differ according to the date assembled.
to check the SERIAL number.