43
Connection of stand-alone option units
2.4.6
Connection of the power regeneration converter (MT-RC)
(FR-F720-03160 (FR-F740-01800) or higher)
When connecting a power regeneration converter (MT-RC), perform wiring securely as shown below. Incorrect
connection will damage the regeneration converter and inverter. After connecting securely, set "1" in
Pr. 30
Regenerative function selection
and "0" in
Pr. 70 Special regenerative brake duty
.
CAUTION
⋅
When using the FR-F700 series together with the MT-RC, install a magnetic contactor
(MC) at the input side of the inverter so that power is supplied to the inverter after 1s
or more has elapsed after power-ON the MT-RC. When power is supplied to the
inverter prior to the MT-RC, the inverter and the MT-RC may be damaged or the
MCCB may trip or be damaged.
⋅
Refer to the MT-RC manual for precautions for connecting the power coordination
reactor and others.
♦
Parameters referred to
Pr. 30 Regenerative function selection, Pr. 70 Special regenerative brake duty
DCL
P1
P1
R/L1
S/L2
T/L3
R1/L11
S1/L21
R
S
T
R
S
T
R1
S1
R2
S2
T2
R2
S2
T2
RES
STF
SD
C
B
A
U
V
W
Inverter
MT-RCL
P
P/+ N/-
P
N
RDY
SE
MT-RC
Reset signal
Alarm signal
Ready signal
Three-phase
AC power
supply
MCCB
MC2
IM
MC1
MT-RC power
supply (MC1)
Inverter input power
supply (MC2)
ON
ON
1s or more