104
Setting of acceleration/deceleration time
and acceleration/deceleration pattern
4.7.2
Starting frequency and start-time hold function (Pr. 13, Pr. 571)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 192)
You can set the starting frequency and hold the set starting frequency for a certain period of time.
Set these functions when you need the starting torque or want to smooth motor drive at a start.
Parameter
Number
Name
Initial Value
Setting Range
Description
13
Starting frequency
0.5Hz
0 to 60Hz
Frequency at start can be set in the
range 0 to 60Hz.
You can set the starting frequency at
which the start signal is turned ON.
571
Holding time at a start
9999
0.0 to 10.0s
Set the holding time of
Pr. 13 Starting
frequency
.
9999
Holding function at a start is invalid
(1) Starting frequency setting
(Pr. 13)
⋅
Frequency at start can be set in the range 0 to 60Hz.
⋅
You can set the starting frequency at which the start signal is
turned ON.
CAUTION
The inverter will not start if the frequency setting signal is less than the value set in
Pr. 13
.
For example, when 5Hz is set in
Pr. 13
, the motor will not start running until the frequency setting signal reaches 5Hz.
(2) Start-time hold function
(Pr. 571)
⋅
This function holds the output frequency set in
Pr. 13 Starting
frequency
during the period set in
Pr. 571
.
⋅
This function performs initial excitation to smooth the motor drive
at a start.
CAUTION
⋅
When the start signal was turned OFF during start-time hold, deceleration is started at that point.
⋅
At switching between forward rotation and reverse rotation, the starting frequency is valid but the start-time hold function is
invalid.
CAUTION
Note that when
Pr. 13
is set to any value lower than
Pr. 2 Minimum frequency
, simply turning ON the start signal
will run the motor at the preset frequency even if the command frequency is not input.
♦
Parameters referred to
♦
Pr.2 Minimum frequency
Refer to page 87
Output
frequency
(Hz)
Time
60
Pr.13
Setting range
STF
ON
0
Output
frequency
(Hz)
Time
Pr. 13
Pr. 571
setting time
STF
ON
0
60
Setting range
REMARKS
When
Pr. 13
= "0Hz", the starting frequency is held at 0.01Hz.
Summary of Contents for -NAFR-F720-00167-NA
Page 22: ...12 MEMO ...
Page 364: ...354 MEMO ...
Page 378: ...368 MEMO ...
Page 396: ...386 MEMO ...