5 - 24 5 - 24
MELSEC-A
5 PROGRAMMING
(3) Initial
settings
Remote Device Station
Setting Item
Settings
A/D conversion enable/prohibit
specification (RWw0)
A/D conversion enable channel:
Channel 1, 2
CH. 1 to CH. 4 input range
setting (RWw1)
Channel 1: 0 to 5V
Channel 2: User range setting 1
Average processing specification
(RWw3)
Channel 1: Sampling
processing
Channel 2: Average processing,
number of times averaging
AJ65VBTCU-68ADV
CH. 2 average time, number of
times setting (RWw5)
Number of average processing
times of channel 2: 16 times
Analog output enable/prohibit
setting (RWw8)
Channel 1, 2: Enable
CH. 1 to CH. 4 output range
setting (RWw9)
Channel 1: 0 to 5V
Channel 2: User range setting 1
AJ65VBTCU-68DAVN
HOLD/CLEAR setting (RWwB)
Channel 1, 2: CLEAR
(4) Other
settings
Remote Device Station
Setting Item
Settings
CH. 1 digital value (RWw0)
500
CH. 2 digital value (RWw1)
1000
CH. 1 analog output
enable/prohibit flag (RY00)
Enable
AJ65VBTCU-68DAVN
CH. 2 analog output
enable/prohibit flag (RY01)
Enable
POINT
When using the AJ65VBTCU-68DAVN as the ver. 2 remote device station in the
normal mode, set the mode select switch to "3".