3 - 11 3 - 11
MELSEC-A
3 SPECIFICATION
(2) Remote I/O signal list for ver. 2 remote device station (ver. 2
compatible slave station) setting
Table 3.6 indicates the assignment and names of the remote I/O signals for ver.
2 remote device station (ver. 2 compatible slave station) setting.
Table 3.6 Remote I/O Signal List for Ver. 2 Remote Device Station
(Ver. 2 Compatible Slave Station) Setting
Signal Direction: AJ65VBTCU-68DAVN Master Module
Signal Direction: Master Module AJ65VBTCU-68DAVN
Remote input (RX)
Name
Remote output (RY)
Name
RYn0
CH.1 analog output enable/disable flag
RYn1
CH.2 analog output enable/disable flag
RYn2
CH.3 analog output enable/disable flag
RYn3
CH.4 analog output enable/disable flag
RYn4
CH.5 analog output enable/disable flag
RYn5
CH.6 analog output enable/disable flag
RYn6
CH.7 analog output enable/disable flag
RYn7
CH.8 analog output enable/disable flag
RXn0
to
RXnB
Reserved
RXnC
E
2
PROM write error flag
RXnD
to
RX (n+1) 7
Reserved
RYn8
to
RY (n+1) 7
Reserved
RX (n+1) 8
Initial data processing request flag
RY (n+1) 8
Initial data processing complete flag
RX (n+1) 9
Initial data setting complete flag
RY (n+1) 9
Initial data setting request flag
RX (n+1) A
Error status flag
RY (n+1) A
Error reset request flag
RX (n+1) B
Remote READY
RX (n+1) C
to
RX (n+3) F
Reserved
RY (n+1) B
to
RY (n+3) F
Reserved
POINT
The reserved devices given in Table 3.6 are used by the system and cannot be
used by the user.
If the user has used (turned on/off) any of them, we cannot guarantee the functions
of the AJ65VBTCU-68DAVN.