5 PROGRAMMING
5.2.3 Program Example for Use of the QnACPU
GX Developer is used to set the network and automatic refresh parameters.
(1) Parameter
setting
(a) Network parameter setting
(b) Automatic refresh parameter setting
POINT
When the QnACPU is used, using "Y" as the remote output (RY) refresh device of
the automatic refresh parameter may not hold the analog value even for the HOLD
setting.
For the HOLD setting, use "M" or "B" as the remote output (RY) refresh device.