5 - 3 5 - 3
MELSEC-A
5 PROGRAMMING
POINT
Some CPU modules may not accept the devices used in the program example in
this chapter. For the setting ranges of the devices, refer to the user's manual of the
CPU module used. For the A1SCPU, for example, devices X100, Y100 and later
are unusable. Use such devices as B and M.
(3) Initial settings
Setting Item
Settings
Analog output enable/disable
setting (RWw2)
Channels 1, 2: enable
CH. 1 to CH. 4 output range
setting (RWw9)
Channel 1: 0 to 5V
Channel 2: user range setting 1
HOLD/CLEAR setting (RWwB)
Channels 1, 2: CLEAR
(4) Other settings
Setting Item
Settings
CH.1 digital value (RWw0)
500
CH.2 digital value (RWw1)
1000
CH.1 analog output
enable/disable frag (RY00)
Enable
CH.2 analog output
enable/disable frag (RY01)
Enable